Permit: T03CM00549

Parcel: 138243870


Addresses:

6655 S HARD ROCK WY

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
05/16/2003 BUILDING - FINAL Approved IVRS - Inspection 0000*
05/13/2003 BUILDING - FINAL Denied IVRS - Inspection 0999*/ 1) EXCESSIVE OVER CURRENT PROTECTION ON A/C. MAXIMUM ALLOWED 40 AMP-50 AMP INSTALLED 2) NO GROUND SYSTEM GROUND RODS NOT INSTALLED 3) ATTIC ACCESS FROM BEDROOM, NOT PERMITTED PER DAVE MANN