Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 05/16/2003 |
BUILDING - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 05/13/2003 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) EXCESSIVE OVER CURRENT PROTECTION ON A/C. MAXIMUM ALLOWED 40 AMP-50 AMP INSTALLED 2) NO GROUND SYSTEM GROUND RODS NOT INSTALLED 3) ATTIC ACCESS FROM BEDROOM, NOT PERMITTED PER DAVE MANN |