Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T03CM00548

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
07/08/2003 MECHANICAL - INTERMEDIATE Approved
05/09/2003 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection 0000*All floors provide access panels in duct for fire dampers. Need to damper opening into elec. room 4th floor. O.K. for ceiling tiles 4th floor except in corridor. Provide clear access to VAV boxes. Provide means to service or replace fire damper motors on 4th floor.