Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 02/11/2003 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 02/10/2003 |
FRAMING |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) 220V CIRCUIT FOR A.C. MUST BE 4 WIRE OUTLET 2) CONVENIENCE OUTLETS REQUIRED WITHIN 6 FEET OF DOOR WAYS EACH SIDE AND 12' THEREAFTER 3) MAKE UP (CONNECT) ALL GROUNDS IN BOXES AND SECURE WITH A MECHANICAL FASTENER |