Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T03CM00544

Parcel: 135074570


Addresses:

8060 E RESEARCH CT


Inspection Status: Approved

Inspection History: ELECTRIC - UFER

Permit Number - T03CM00544

Inspection Description - ELECTRIC - UFER

Inspection Status - Approved

Date Description Inspector Results Comments
05/14/2003 ELECTRIC - UFER Approved IVRS - Inspection 0000*#4/0 STRANDED WIRE COUPLED TO 20' REBAR IN BOTTOM 1/3 OF FOOTING. PLAN CALLS FOR 3/0.