Permit: T03CM00544

Parcel: 135074570


Addresses:

8060 E RESEARCH CT


Inspection Status: Approved

Inspection History: STEM WALL/RETAINING WALL

Permit Number - T03CM00544

Inspection Description - STEM WALL/RETAINING WALL

Inspection Status - Approved

Date Description Inspector Results Comments
06/13/2003 STEM WALL/RETAINING WALL Approved IVRS - Inspection 0000*
06/11/2003 STEM WALL/RETAINING WALL Denied IVRS - Inspection 0999*/ 1) I BELIEVE YOU NEED TO EXTEND DOCK WALL REINFORCEMENT TO WITHIN 2" OF TOP OF WALL. HAVING IT STOP 6" BELOW WITH ADDED FENCE AT HADNRAILS CONTRIBUTING TO LATERAL LOADS COULD CAUSE ?. SEE DETAIL 7/5.3
05/16/2003 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection 0000*COLUMN @ NW CORNER OK TO POUR.
05/14/2003 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection 0000*PANELS 4-10.
1.) MINOR ADJUSTMENT NECESSARY FOR CLEARANCE FROM FORM ON NEARLY ALL PANELS.
2.) PANEL 8 90% COMPLETE.
3.) OK TO POUR WHEN SPECIAL INSPECTOR OBSERVES FULL COMPLIANCE LATER THIS PM.
05/07/2003 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection 0000*PANELS 2,12,14,17 PLEASE MAINTAIN SIDE CLEARANCE TO FORMS WHEN POURING.
04/30/2003 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection 0000*PANELS 1,3,11,13,15,16,18.
2.) MINOR ADJUSTMETNS NECESSARY ON PANELS. OK TO POUR AFTER SPECIAL INSPECTOR VERIFIES.