Inspection History: STEM WALL/RETAINING WALL
Permit Number - T03CM00544
Inspection Description - STEM WALL/RETAINING WALL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/13/2003 | STEM WALL/RETAINING WALL | Approved | IVRS - Inspection 0000* | |
06/11/2003 | STEM WALL/RETAINING WALL | Denied | IVRS - Inspection 0999*/ 1) I BELIEVE YOU NEED TO EXTEND DOCK WALL REINFORCEMENT TO WITHIN 2" OF TOP OF WALL. HAVING IT STOP 6" BELOW WITH ADDED FENCE AT HADNRAILS CONTRIBUTING TO LATERAL LOADS COULD CAUSE ?. SEE DETAIL 7/5.3 | |
05/16/2003 | STEM WALL/RETAINING WALL | Partial Approval | IVRS - Inspection 0000*COLUMN @ NW CORNER OK TO POUR. | |
05/14/2003 | STEM WALL/RETAINING WALL | Partial Approval | IVRS - Inspection 0000*PANELS 4-10. 1.) MINOR ADJUSTMENT NECESSARY FOR CLEARANCE FROM FORM ON NEARLY ALL PANELS. 2.) PANEL 8 90% COMPLETE. 3.) OK TO POUR WHEN SPECIAL INSPECTOR OBSERVES FULL COMPLIANCE LATER THIS PM. |
|
05/07/2003 | STEM WALL/RETAINING WALL | Partial Approval | IVRS - Inspection 0000*PANELS 2,12,14,17 PLEASE MAINTAIN SIDE CLEARANCE TO FORMS WHEN POURING. | |
04/30/2003 | STEM WALL/RETAINING WALL | Partial Approval | IVRS - Inspection 0000*PANELS 1,3,11,13,15,16,18. 2.) MINOR ADJUSTMETNS NECESSARY ON PANELS. OK TO POUR AFTER SPECIAL INSPECTOR VERIFIES. |