Inspection History Details
Inspection Status: Approved
Inspection History: STEM WALL/RETAINING WALL
Permit Number - T03CM00543
Inspection Description - STEM WALL/RETAINING WALL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/27/2003 | STEM WALL/RETAINING WALL | Approved | IVRS - Inspection 0000* | |
04/30/2003 | STEM WALL/RETAINING WALL | Partial Approval | IVRS - Inspection 0000*1.) PANELS 1-8,10,12,15,20. BLD. A 2.) MISSING STEEL IN PANEL #1 & #20 BEING PLACED AT THIS TIME. 3.) PIER/JAMB DETAIL 11/5-3 REQUIRES 3/4" CLEAR @ EACH FACE. #3 RINGS FABRICATED TOO LARGE FOR OPENING. ENGINEER MR. HARRIS ON SITE HE IS ALLOWING RINGS TO BE "RACKED" IN ORDER TO PROVIDE PROPER CLEARANCE. 4.) THE 2 EA #S BARS AROUND OPENINGS ARE ALLOWED TO BE BUNDLED PER CONVERSATION WITH ENGINEER @ SITE. 5.) PANELS MAY BE POURED WHEN ENGINEER INSPECTION CONDFIRMS CLEARANCES OF PIER PANELS. |
|
04/23/2003 | STEM WALL/RETAINING WALL | Partial Approval | IVRS - Inspection 0000* |