Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T03CM00536
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/07/2003 | PLUMBING - FINAL | Approved | IVRS - Inspection 0000*P-2 REVISED GAS DIAGRAM DEFINITELY SHOWS DEMO'D GAS HEADER AND NEW GAS PIPING BECAUSE PART OF THE SYSTEM INCORPORATION WELDED GAS PIPING A 60# TEST IS REQUIRED. THIS IS NO JUST A RECONNECT. 2.) CORRECTION MADE OK CONTRACTOR TO REPAIR LEAK AT GARAGE DISPOSER. 3.) OWNER HAS COPIES OF APPROVALS OF ALL REQUIRED INSPECTIONS. OK TO RE-ENGERGIZE GAS NO GAS CARD LEFT AT METER. 4.) OK FOR C OF O PENDING ANY OTHER INSPECTIONS. |
|
05/06/2003 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999*1.) GAS TURNED ON BY SW GAS BEFORE GAS CARD WAS ISSUED HAS NOT PASSED PRESSURE TEST. 2.) INDIRECT WASTE PIPING BETWEEN 5-15 FEET REQUIRES TRAP. 3.) WHEELED GAS APPLIANCES REQUIRE CABLE RESTAINT. 4.) CORRECT BACK PITCH AT DISHWASHER AND USE APPROVED FITTINGS. |