Permit: T03CM00525

Parcel: 121012610


Addresses:

5927 E PIMA ST

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
06/12/2003 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
06/10/2003 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*/ 1) PROTECT CABLES AT STOPS 300-4 AND PVC CONDUIT 2) SUPPORT CONDUIT IN STUDS ON VERTICAL RISE 3) SUPPORT NM CABLE AS PER CODE 12" AND 4 1/2" 336.18 4) USE AN APPROVED CONNECTOR AT CABINETS