Permit: T03CM00514

Parcel: 107142420


Addresses:

266 W GRANT RD


Inspection Status: Not ready for Inspection

Inspection History: MECHANICAL - HOODS

Permit Number - T03CM00514

Inspection Description - MECHANICAL - HOODS

Inspection Status - Not ready for Inspection

Date Description Inspector Results Comments
08/10/2012 MECHANICAL - HOODS Not ready for Inspection THIS HAS OTHER HISTORY FOR DENIED ELECTRICAL. PROVIDE ELECTRICAL HISTORY. PLEASE CHECK ALL HISTORY
02/17/2012 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
1) REMOVE ANY SHARP EDGES ON STAINLESS STEEL
09/16/2011 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
08/03/2011 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
02/10/2011 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
04/09/2010 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
1) OK TO PROCEED WITH FIRE SUPRESSION SYSTEM
10/30/2009 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
1) PROVIDE GREASE THRU FOR FILTERS
05/20/2009 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
INSTALL MUA PER OUR CONVERSATION
REPAIR CRACKS IN HOODS
SEAL HOOD AND WALL FLASHING AS NEEDED
11/24/2008 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
PROVIDE MAKE UP AIR DUCT
11/21/2008 MECHANICAL - HOODS Denied IVRS - Inspection :
See detailed listing on site.| 999*
CALLED AT 8:55 LEFT MESSAGE FOR 30 MIN. LEAD TIME SHOWED UP AT 9:46 -- NO ONE ON SITE
05/28/2008 MECHANICAL - HOODS Cancelled IVRS - RI canceled
05/28/2008 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
DUCT WRAP OK, OK TO HANG HOODS
01/25/2008 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
MAKE UP AIR ATTACHED TO FRONT OF HOOD OK
NOT REQUIRED TO HEAT MAKE UP AIR
07/27/2007 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
MAKE UP AIR MUST COMPLY WITH SECTION 508.1.1 2003 IMC
PROVIDE DUCT HEATERS FOR EVAP COOLERS OR PROVIDE COMPENSATING HOODS.

CHECKED WELDS ON GREASE DUCTS. OK TO PROCEED.

YOU COULD ALSO INSTALL DIFFUSERS AGAINST THE HOOD WITH A GRILLE THAT WOULD SPREAD THE AIR ACROSS THE CEILING.
02/05/2007 MECHANICAL - HOODS Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PLANS DO NOT SHOW ANY DETAILS OR PLAN FOR TYPE I HOODS, MAKE UP AIR, EXHAUST FANS
2) WALL AND CEILING ARE WOOD FRAMED NEED 18" CLEARANCE-ONLY 1 HOOD IS COMPENSATING
3) PROVIDE AN ENGINEERED PLAN APPROVED BY THE CITY OF TUCSON
4) HOODS ARE 8' LONG EACH