Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESS TEST FNL
Permit Number - T03CM00514
Inspection Description - PLUMBING - GAS PRESS TEST FNL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/30/2004 | PLUMBING - GAS PRESS TEST FNL | Approved | IVRS - Inspection :* 1) GREASE TRAP INSTALLED OK TO COVER | |
09/27/2004 | PLUMBING - GAS PRESS TEST FNL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/1)PLUMBER MUST BE PRESENT AT TIME OF NEXT INSPECTION. (TELL HIM TO BRING A COPY OF HIS LICENSE) 2)CONTRACTOR TO PAY REINSPECTION FEE. |
|
09/24/2004 | PLUMBING - GAS PRESS TEST FNL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/REMOVE BACK PITCHED SECTION OF VENT. |
|
09/23/2004 | PLUMBING - GAS PRESS TEST FNL | Not ready for Inspection | IVRS - Inspection :*/1)VENT GREASE TRAP NOT DRAIN LINE WHERE A VENT CONNECTS TO A HORIZONTAL DRAIN LINE, THE INVERT SHALL BE ABOVE THE DRAINAGE CENTER LINE, DOWN STREAM OF THE TRAP BEING SERVED. | |
09/20/2004 | PLUMBING - GAS PRESS TEST FNL | Not ready for Inspection | IVRS - Inspection :*/1)A SANTEL? MAY NOT LAY ON ITS BACK 2)VENT TO BE TAKEN OFF DOWNSTREAM OF THE TRAP 3)MAY NOT REDUCE THE OUTLET OF THE TRAP 4)A NOHUB BAND IS NOT APPROVED FOR ABS 5)GREASE TRAP NOT LEVEL 6)VENT TO BE EXTENDED TO ABOVE PARAPET 7)REMEMBER, ABS REQUIRES 12" OF COVER 8)GREASE TRAP INSTALLED BACKWARDS |