Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/17/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MENU BOARD OUTSIDE HAS NOT ELECTRICAL PIPING USED AS CONDUIT (WATER PIPE) 2) 2 SERVICES ON BLDG SAME ADDRESS, GROUND WIRES CUT 3) SIGN OUTSIDE NOT TO CODE 4) PROVIDE LADDER FOR ROOF INSPECTION 5) BOND GEC AND NEUTRAL IN SERVICE DISCONNECT 6) 110V RECEPTS IN KITHEN NEED TO BE GFI PROTECTED PER 210.8 NCER 7) DINING AREA LTG AND FANS NOT ON PLAN 8) ELECTRICAL APPLIANCES TO BE LISTED/MARKED PER 110.3-422 NEC 9) COMPLETE INSPECTION NOT POSSIBLE DUE TO MISC. EQUIP IN WAY |