Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 04/30/2003 |
FRAMING |
|
Approved |
IVRS - Inspection 0000*/ 1) RE-INSPECT |
| 04/29/2003 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) NO TRUSS DRAWINGS ON SITE. TRUSS BRACE IN GARAGE APPEARS TO BE MISSING 2) DOUBLE TOP PLATE JOINTS MUST BE STAGGARD 4' ON CENTER 3) RANGE HOOD 26 GUAGE MUST EXTEND THRU CEILING 4) ANCHOR BOLTS REQUIRED WITHIN 12" OF SPLICES |
| 04/28/2003 |
FRAMING |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) SECURE RANGE VENT INTO WALL 2) COMPLETE STUCCO |