Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T03CM00507
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/01/2003 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection 0000* 1.) ABS DWV THRU ROOF OK 2.) COPPER IN WALLS OK PLEASE ALLOW PLUMBER TIME TO INSULATE HOT LINE BEFORE SHEET ROCK. 3.) CLOSET FLANGES OK 4.) OK TO COVER WALLS. |
|
| 03/31/2003 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999*1.) A CONDENSATE DRAIN LINE MAY NOT TERMINATE AT A SINK TAILPIECE. 2.) AGGREGATE CROSS SECTIONAL AREA OF VENTING MUST EQUAL THE LARGEST REQUIRED BLDG SEWER AREA. TWO TWO INCH VENTS EQUAL 6.28 2" INADEQUATE. 3.) NO PROVISION MADE FOR INSULATION ON WATER PIPING. |