Inspection Status: Approved
Inspection History: SHEET ROCK NAILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/08/2003 | SHEET ROCK NAILING | Approved | IVRS - Inspection 0000* | |
| 04/04/2003 | SHEET ROCK NAILING | Partial Approval | IVRS - Inspection 0000*FIREWALL COMPLETE 80% DOWNSTAIRS. | |
| 04/02/2003 | SHEET ROCK NAILING | Partial Approval | IVRS - Inspection 0000*I NEED FIRE STOP SYSTEM BEING USED FOR THIS PROJECT. | |
| 04/01/2003 | SHEET ROCK NAILING | Partial Approval | IVRS - Inspection 0000*1.) 2nd floor office area ok to tape. 2.) provide fire stop system. 3.) warehouse side still requires fire safeing o all penetration and gaps over 1/16". |