Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 08/07/2003 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*/ 1) OK FINAL |
| 08/05/2003 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) FITTINGS WITH #4 AND LARGER TO BE INSULATED WITH FITTING OR BUSHING 2) TIGHTEN LOOSE SEAL TITE FITTINGS IN A/C UNITS |
| 07/28/2003 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) NO WORK PROGRESS |
| 07/24/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/1) MAINTAIN WORKING CLEARANCES AT TRASH COMPACTOR DISSCONNECT. 2) WE HAVE MULTIPLE TERMINATIONS AT GROUND LUG. 3) FILL UNUSED OPENINGS IN CONTROL SWITCH. PLEASE PROVIDE ACCESS INTO SOFFIT FOR NEXT INSPECTION. |
| 06/02/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) APPROVED EXTENDER RING ARE NEEDED WHERE MORE THAN 1/4" IN NON COMBUSTIBLES 370-20 2) FILL UNUSED OPENINGS IN LIGHT BOXES 3) CLEAN SURFACE UNDER GROUND LUGS 250-12 4) CORRECTLY IDENTIFY UNDERGROUNDED CONDUCTORS 5) BOND JUNCTION BOX 250-148 6) IS HEATER THERMALLY PROTECTED 7) VERIFY LISTING ON ? PUMP 8) BOND BUSHING OVER 250 VOLT AT TRASH COMPACTOR 9) FINISH EQUIPMENT INSTALLATION 10) PROVIDE REVISED PLANS |