Permit: T03CM00504

Parcel: 13102149M


Addresses:

1415 S WOODLAND AV

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
05/07/2003 PLUMBING - INTERMEDIATE Approved IVRS - Inspection 0000*SOIL WATER TEST IS OK
2.) P.O.C. OF NEW BLDG. DRAINS TO EXSISTING BLDG. DRAIN IS OK
3.) OK TO DRYWALL.
04/30/2003 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0999*
1.) MUST PROVIDE WATER TEST ON NEW WASTE & VENT SYSTEM.
2.) CAN NOT USE NO HUB COUPLING FOR ABS MATERIAL.
3.) CAN NOT HAVE C.O. TEE ON A HORIZONTAL POSITION.
4.) CAN NOT WET VENT 2" TRAP ARM TO A 2" BARREL.
5.) CAN NOT RUN A 2" TRAP ARM FOR KITCHEN SINK THEN STUBB OUT 1 1/2 SEE SECTION: 1003.3 94 UPC.
6.) MUST GET A REVISED DRAWING FOR SIZE OF TRAP ARM TO WET VENTED SYSTEM SEE SECTION: 908.2 94 UPC.
7.) DO NOT COVER.
03/27/2003 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0999* 1) MUST PROVIDE A WATER TEST ON NEW WASTE & VENT SYSTEM 2) THIS WASTE & VENT SYSTEM IS NOWHERE NEAR TO CODE 3) WILL REQUIRE A REVISED & APPROVED PLAN ON WATER & VENT SYSTEM. APPROVED DRAWINGS ON SITE WAS APPROVED ON ERROR. 4) DO NOT COVER
03/25/2003 PLUMBING - INTERMEDIATE Denied IVRS - Inspection 0999*DOOR WAS LOCKED.