Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/07/2003 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection 0000*SOIL WATER TEST IS OK 2.) P.O.C. OF NEW BLDG. DRAINS TO EXSISTING BLDG. DRAIN IS OK 3.) OK TO DRYWALL. |
|
| 04/30/2003 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999* 1.) MUST PROVIDE WATER TEST ON NEW WASTE & VENT SYSTEM. 2.) CAN NOT USE NO HUB COUPLING FOR ABS MATERIAL. 3.) CAN NOT HAVE C.O. TEE ON A HORIZONTAL POSITION. 4.) CAN NOT WET VENT 2" TRAP ARM TO A 2" BARREL. 5.) CAN NOT RUN A 2" TRAP ARM FOR KITCHEN SINK THEN STUBB OUT 1 1/2 SEE SECTION: 1003.3 94 UPC. 6.) MUST GET A REVISED DRAWING FOR SIZE OF TRAP ARM TO WET VENTED SYSTEM SEE SECTION: 908.2 94 UPC. 7.) DO NOT COVER. |
|
| 03/27/2003 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999* 1) MUST PROVIDE A WATER TEST ON NEW WASTE & VENT SYSTEM 2) THIS WASTE & VENT SYSTEM IS NOWHERE NEAR TO CODE 3) WILL REQUIRE A REVISED & APPROVED PLAN ON WATER & VENT SYSTEM. APPROVED DRAWINGS ON SITE WAS APPROVED ON ERROR. 4) DO NOT COVER | |
| 03/25/2003 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999*DOOR WAS LOCKED. |