Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T03CM00495
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/13/2003 | ELECTRIC - INTERMEDIATE | Approved | ||
02/07/2003 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0999*1.) NEED LETTER FROM TUCSON MALL MANAGEMENT STATING THAT THEY ALLOW THE USE OF METAL CLAD CABLE AS A PERMANENT WIRING METHOD. 2.) NEED LETTER FROM ENGINEER OF RECORD STATING THAT M.C. CABLE MAY BE USED IN LEIU OF CONDUIT. THE COVERING UP OF UNAPPROVED WORK IS COUNTER TO THE UNIFORM ADMINISTRATIVE CODE. DO NOT CONTINUE TO REPEAT THIS ERROR. MY NOTE TO YOU ON 2-6-03 WAS VERY CLEAR THAT DRYWALL WAS TOBE LEFT OFF UNTIL THE WORK WAS APPROVED BY ALL PARTIES TO THE PROJECT. |
|
02/06/2003 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0925*/ 1) NO PLANS OR OTHER INFO ON SITE. RECALL INSPECTION. DO NOT DRYWALL W/O INSPECTION |