Permit: T03CM00402

Parcel: 137314470

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
04/02/2003 FRAMING Approved IVRS - Inspection 0000*
03/24/2003 FRAMING Partial Approval IVRS - Inspection 0000*/ 1) OK TO INSULATE AND SHEETROCK OTHER AREAS
03/20/2003 FRAMING Denied IVRS - Inspection 0999*/ 1) FIRE BLOCK CHASE AT RANGE HOOD 2) KITCHEN DIRTY ARM LEAK AT SAN-T 3) PROVIDE ATTIC ACCESS 4) REVISE ELECTRIC PLAN FOR ADDED 220 VAC CIRCUIT IN GARAGE