Permit: T03CM00400

Parcel: 11440286Q


Addresses:

6417 E GRANT RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/21/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
02/20/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
02/04/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*1.) CORD CAN NOT PASS THROUGH CEILING TILE OR BE ABOVE CEILING 400-7 & 400-8.
2.) TIGHTEN LOOSE SEAL TITE FITTINGS.
3.) USE PROPER COLOR CODING FOR GROUNDED CONDUCTORS IN RACEWAY SYSTEM 200-6.
4.) CONDUIT RUN NOT TO HAVE MORE THAN 360 IN RUN.
5.) FILL ALL UNUSED OPENING IN PANEL.
6.) THE BREAKER MUST BE LISTED FOR USE BY MANUFACTURE AND SIZED FOR CONDUCTOR AMPACITY.
7.) PANEL IS INSTALL AGAINST CODE WITH MULITPOLE TERMANATIONS OFF OF MAIN DISCONNECT. ALSO IS NOT SECURED TO STRUCTURE.