Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/21/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
| 02/20/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* | |
| 02/04/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*1.) CORD CAN NOT PASS THROUGH CEILING TILE OR BE ABOVE CEILING 400-7 & 400-8. 2.) TIGHTEN LOOSE SEAL TITE FITTINGS. 3.) USE PROPER COLOR CODING FOR GROUNDED CONDUCTORS IN RACEWAY SYSTEM 200-6. 4.) CONDUIT RUN NOT TO HAVE MORE THAN 360 IN RUN. 5.) FILL ALL UNUSED OPENING IN PANEL. 6.) THE BREAKER MUST BE LISTED FOR USE BY MANUFACTURE AND SIZED FOR CONDUCTOR AMPACITY. 7.) PANEL IS INSTALL AGAINST CODE WITH MULITPOLE TERMANATIONS OFF OF MAIN DISCONNECT. ALSO IS NOT SECURED TO STRUCTURE. |