Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/03/2003 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection 0000* | |
| 02/28/2003 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000*1.) SUPPORT ELECTRICAL CHASE AT TOP AND BOTTOM FOR CASH WRAP. 2.) M/C CABLE TO BE SUPPORTED AS PER CODE. 3.) PLEASE SUPPORT VDV CABLES UP OFF OF GRID AS PER CODES AND PROTECT CABLES FROM SHARP METAL EDGES. 4.) MAINTAIN WORKING SPACE ABOUT WRITE HEATER DISCONNECT 5.) PROVIDE A BUSHING TO PROTECT CONDUCTOR TO W/H DISCONNECT. 6.) WHERE ARE GFI RECEPTICALS AS PER PLAN? 7.) SUPPORT OUTLET BOX IN CEILING |