Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/12/2004 | MECHANICAL - FINAL | Approved | IVRS - Inspection :*/ 1) OK FOR FINAL | |
| 07/22/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) GAS FLEX CONNECTOR CANNOT EXCEED 3' IN LENGTH 2) SECURE ELECTRIC DISCONNECT. PROVIDE ROOF JACKS AT ROOF PENETRATIONS 3) PROVIDE A HOSE CLAMP ON CONDENSATE FINAL CONNECTION |
|
| 07/20/2004 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :*/ 1) INCORRECT SIZE GAS LINE (FLEX) 2) PAINT PVC COND 3) BLOCK/ CLAMP ELECTRIC CIRCUIT FLEX |