Date Description Inspector Results Comments
06/18/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*/ 1) OK TO CLEAR 2) REVISION WAS SUBMITTED AND APPROVED
06/17/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*/ 1) FINISH TERMANTIONS 2) BONDING JUMPERS TO BE SIZED PER 250-102 AND 250-66 3) CONNECT GROUNDING ELECTRODE TO GROUNDED CONDCTOR 4) BONDING DEVICE NEEDED AT METAL RISER 5) SEALING DEVICE FOR ENTRANCES ABOVE CORRECT CARRING PARTS 6) PLEASE HAVE PLANS THAT ARE REFLECTIVE OF WORK INSTALLED