Permit: T03CM00366

Parcel: 123111210

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T03CM00366

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
05/19/2003 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection 0000*
05/18/2003 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection 0999*/ 1) PLAN APPROVED IN ERROR. ONLY 3 WATER CLOSETS MAY BE DRAINED BY A 3" LINE (HORIZONTAL) 2) WHERE A VENT CONNECTS TO A HORIZONTAL DRAIN LINE, IT SHALL HAVE IT'S INVERT TAKEN OFF ABOVE THE DRAINAGE CENTER LINE, DOWN STREAM OF THE TRAP BEING SERVED 3) YARD WATER NOT INSTALLED