Permit: T03CM00355

Parcel: 14117005D

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T03CM00355

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
04/03/2003 FRAMING Approved
04/02/2003 FRAMING Partial Approval IVRS - Inspection 0000*/ 1) FIRE BLOCKING IN BEDROOM #4 CLOSET NOT CORRECTED, NEXT FAILURE WILL RESULT IN A RE-FEE 2) 3035 PLUMBING INTER NEED TO BE RESOLVED WITH OTHER INSPECTION TO ENTER INTO IVR
04/01/2003 FRAMING Partial Approval IVRS - Inspection 0000*/ 1) NO TEST ON VENTS (DWV'S) 2) PARTIAL FRAMING PENDING 3035 APPROVAL FROM RAF.
03/31/2003 FRAMING Denied IVRS - Inspection 0999*/ 1) USE PROPER NAIL PROTECTION AT DRYER VENT 2) DWV'S FAILED TEST 3) FIRE BLOCK AT 4TH BEDROOM CLOSET AND 2ND BEDROOM CLOSET 4) DUCT WORK AT HALL NOT COMPLETED 5) NAIL PROTECT ELECTRICAL WIRE SOUTHWEST CORNER FROM OUTSIDE AND RIGHT SIDE REAR DOOR DOUBLE TOP PLATE AT GREAT ROOM 6) NAIL PROTECT COPPER LINES AT KITCHEN AND FRIDGE LINE
03/28/2003 FRAMING Not ready for Inspection IVRS - Inspection 0000*/ 1) NAIL IN ISLAND SINK DRAIN PIPE 2) PAD 2 X 4 AT REFRIDGERATOR LINE 3) TIGHTEN NUT AT GARAGE TO HOUSE SHEAR 4) REATTACH CROSS BRACE FRONT GABLE AT ATTIC VENT 5) BANG PLATE SHOWER REAR WEST VENT ROMEX TOP PLATE REAR BEDROOM 6) NOTCH DOUBLE TOP PLATE FRONT GIRDER INTER. BEARING