Permit: T03CM00351

Parcel: 12809015A

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
02/05/2003 PLUMBING - FINAL Approved 1.) PLBG INAL IS OK
2.) OK FOR C OF O.
02/04/2003 PLUMBING - FINAL Denied IVRS - Inspection 0999*
1.) 2" WATER LINE FOR SINK IS OK
2.) OK TO BACKFILL TRENCH.
3.) MUST SEAL PENETRATION OF 2" WASTE INTO BLDG.
4.) MUST SECURE HOT & COLD WATER LINES UNDER CABINET.
01/31/2003 PLUMBING - FINAL Denied 1.) MUST PROVIDE C.O. FOR HAND SINK
2.) 2" WASTE LINE REQUIRES 1/4" PER FT. OF GRADE.
3.) CAN NOT USE COMBO IN A VERTICAL POSITION. WHEN COMBO IS IN THIS POSITION THE OUTLET OF VENT IS LOWER THAN TRAP.
4.) MUST USE C.I. FOR VENT AND EXPOSED WASTE LINES.