Permit: T03CM00346

Parcel: 125042790

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
02/10/2004 BUILDING - FINAL Approved IVRS - Inspection 0000*
02/09/2004 BUILDING - FINAL Not ready for Inspection IVRS - Inspection 0000*
02/05/2004 BUILDING - FINAL Denied IVRS - Inspection 0999*/ 1) CORRECT BATH GFI'S 2) PROTECT NORTH KITCHEN COUNTER OUTLETS WITH GFI'S 3) HARD PIPE WATER HEATER TRP DRAIN (NO FLEX) AND WIRE FOR OPERATION 4) INTER-CONNECT SMOKIES 5) HEAT PUMPS ARE OVER FUSED-30 MAX 6) NEED BACK FLOW VALVE ON HOSE BIB 7) 1ST FLOOR PANEL-MATCH WIRE SIZE TO BREAKERS AND INSTALL BUSHING IN PANEL BOTTOM KNOCKOUT 8) 2ND FLOOR PANEL-CHANGE WATER HEATER TO 30 AMP DOUBLE POLE 9) TOP STAIR RISER IS 1 1/4" HIGHER THAN THE REST