Permit: T03CM00320

Parcel: 12212052A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T03CM00320

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/10/2005 ELECTRIC - FINAL Approved IVRS - Inspection :* OK FINAL
02/07/2005 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :* NOT READY OK TEMP POWER FOR TEST SUBJECT TO BOND. 1) WATER HEATER TO HAVE DISCONNECTING MEANS OR CAPABLE TO BE LOCKED OUT ALSO TIGHTEN LOOSE FITTING. 2) PLEASE LABEL BREAKERS. 3) BOXES NOT TO BE MORE THAN 1/4" FROM BOX TO SURFACE 370-20/413.20 AN APPROVED EXTENDER RING MAY BE USED. ROOF: 1) SHEET METAL SCREWS NOT ALLOWED FOR GROUNDING AND CLEAN SUFACE UNDER LUG 2) IDENTIFY UNGROUNDED CONDUCTORS IN JUNCTION BOX 200-7 ( 210-5 (C)) 3) PLEASE IDENTIFY A/C ?? GROUPED TOGETHER