Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T03CM00320
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/10/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* OK FINAL | |
02/07/2005 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* NOT READY OK TEMP POWER FOR TEST SUBJECT TO BOND. 1) WATER HEATER TO HAVE DISCONNECTING MEANS OR CAPABLE TO BE LOCKED OUT ALSO TIGHTEN LOOSE FITTING. 2) PLEASE LABEL BREAKERS. 3) BOXES NOT TO BE MORE THAN 1/4" FROM BOX TO SURFACE 370-20/413.20 AN APPROVED EXTENDER RING MAY BE USED. ROOF: 1) SHEET METAL SCREWS NOT ALLOWED FOR GROUNDING AND CLEAN SUFACE UNDER LUG 2) IDENTIFY UNGROUNDED CONDUCTORS IN JUNCTION BOX 200-7 ( 210-5 (C)) 3) PLEASE IDENTIFY A/C ?? GROUPED TOGETHER |