Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T03CM00302

Parcel: 11307086A

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
09/23/2003 MECHANICAL - FINAL Approved IVRS - Inspection 0000*
09/18/2003 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*/ ROOF TOP UNITS, PKG, HT/COOL EAST SIDE UNIT - FURNACE VENT DISCHARGING DIRECTLY INTO OAS (OUTSIDE CIR.) OF WEST SIDE UNIT. REROUTE - FURNACE DISCHARGE ABOVE TOP OF UNIT.