Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 06/25/2004 |
PLUMBING - FINAL |
|
Approved |
IVRS - Inspection :*/ 1) PLBG FINAL OK. 2) CORRECTIONS MADE OK. 3) OK FOR C OF O PENDING ANY OTHER INSP. |
| 06/17/2004 |
PLUMBING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection :*/ THERE IS NO SUITE # 163 AT 3055 N. CAMPBELL |
| 06/16/2004 |
PLUMBING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection :* |
| 09/23/2003 |
PLUMBING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 09/22/2003 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999*/1) SOAP DISPENSER AT JANITORS SINK NOT APPROVED, ATMOSPHERIC VACUUM BREAKER INSUFFICIENT FOR CONTAMINATION, SEE TABLE 6-1 94 UPC. 2) HAVE RPZ CERTIFIED BEFORE FINAL. |
| 09/18/2003 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999*/1) INSTALL C.O. ON 3 COMP SINK DRAIN. 2) INSTALL C.O. COVER ( USE COUNTER SUNK TAPPED PLUG) BEHIND FOYER. 3) INSULATION KITS ON HC LARS. 4) ICE BIN AND ICE MAKER TO BE DRAINED SEPARATLY. REMEMBER I.W. LONGER THAN FIVE FEET TO BE DIRECTLY TRAPPED. |