Permit: T03CM00302

Parcel: 11307086A

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
06/25/2004 PLUMBING - FINAL Approved IVRS - Inspection :*/ 1) PLBG FINAL OK. 2) CORRECTIONS MADE OK. 3) OK FOR C OF O PENDING ANY OTHER INSP.
06/17/2004 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*/ THERE IS NO SUITE # 163 AT 3055 N. CAMPBELL
06/16/2004 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
09/23/2003 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection 0000*
09/22/2003 PLUMBING - FINAL Denied IVRS - Inspection 0999*/1) SOAP DISPENSER AT JANITORS SINK NOT APPROVED, ATMOSPHERIC VACUUM BREAKER INSUFFICIENT FOR CONTAMINATION, SEE TABLE 6-1 94 UPC. 2) HAVE RPZ CERTIFIED BEFORE FINAL.
09/18/2003 PLUMBING - FINAL Denied IVRS - Inspection 0999*/1) INSTALL C.O. ON 3 COMP SINK DRAIN. 2) INSTALL C.O. COVER ( USE COUNTER SUNK TAPPED PLUG) BEHIND FOYER. 3) INSULATION KITS ON HC LARS. 4) ICE BIN AND ICE MAKER TO BE DRAINED SEPARATLY. REMEMBER I.W. LONGER THAN FIVE FEET TO BE DIRECTLY TRAPPED.