Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date |
Description |
Inspector |
Results |
Comments |
| 08/03/2003 |
PLUMBING - ROUGH, SOIL |
|
Approved |
IVRS - Inspection 0000*/ 1) FLOOR SINKS AND DRAINS BLOCKED OUT OR INSTALLED OK TRAP PRIMERS-OK 2) CONTRACTORS TO WRAP ALL ABS RISERS PASSING THRU CONCRETE |
| 07/31/2003 |
PLUMBING - ROUGH, SOIL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) ABS DWV UNDERGROUND-OK. WATER TEST ON RISER TO TEN FEET-OK. GREASE TRAP-OK. OK TO BACKFILL 2) NEED TO SEE FLOOR SINKS, FLOOR DRAINS AND TRAP PRIMERS |
| 07/30/2003 |
PLUMBING - ROUGH, SOIL |
|
Denied |
IVRS - Inspection 0999*/ 1) AN ABS BLAKE TEE IS LISTED TO BE USED IN THE VERTICAL POSITION, ABOVE GRADE, AS A SURFACE CLEANOUT 2) SEE INSTALLATION STANDARD FIVE-94 UPC 316.1.5 FEMALE ABS FITTINGS SHALL BE IN AN ACCESSIBLE LOCATION 3) OK TO COVER ALL OTHER AREAS 4) GREASE TRAP OK |