Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/10/2005 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :**APPROVED | |
| 01/04/2005 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : The service entrance is not per code.| 215* 1) CORRECTIONS: THE UFER GROUNDING CONDUCTOR MUST BE RE-ROUTED TO LAND ON THE NEUTRAL OF ONE OF THE METER 1 MAIN/ L.C. THEN TO THE GUTTER BROUNDING TERMINAL AND FROM THERE TO GROUNDING BUSHINGS AND OTHER PANEL (TEP DOESN'T WANT IT IN THEIR TERM ? ) 2) ALL NIPPLES CONTAINING UNFUSED SERVICE CONDUCTORS MUST HAVE GROUNDING BUSHINGS OR OTHER GROUNDING TYPE FITTINGS AT BOTH ENDS |
|
| 01/03/2005 | ELECTRIC - CABLE DROP | Partial Approval |