Permit: T03CM00298

Parcel: 116182780

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Date Description Inspector Results Comments
01/10/2005 ELECTRIC - CABLE DROP Approved IVRS - Inspection :**APPROVED
01/04/2005 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
The service entrance is not per code.| 215*
1) CORRECTIONS: THE UFER GROUNDING CONDUCTOR MUST BE RE-ROUTED TO LAND ON THE NEUTRAL OF ONE OF THE METER 1 MAIN/ L.C. THEN TO THE GUTTER BROUNDING TERMINAL AND FROM THERE TO GROUNDING BUSHINGS AND OTHER PANEL (TEP DOESN'T WANT IT IN THEIR TERM ? )
2) ALL NIPPLES CONTAINING UNFUSED SERVICE CONDUCTORS MUST HAVE GROUNDING BUSHINGS OR OTHER GROUNDING TYPE FITTINGS AT BOTH ENDS
01/03/2005 ELECTRIC - CABLE DROP Partial Approval