Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T03CM00268
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/18/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*/ 1) INSTALL LABEL ON ACCESS DOOR STATING " BLOWER MOTOR CORD DISCONNECT ABOVE ACCESS DOOR" 2) OK FINAL | |
09/16/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*/ 1) PROTECT CONDUCTOR SIZED LARGER 2) INSTALL ALL STRANDS UNDER TERMINAL LUG-DO NOT TRIM STRANDS 3) LABEL PANEL DIRECTORIES UPS PANEL 4) PROTECT CONDUCTORS FROM SHARP METAL EDGES 5) BOND ENCLOSURES 6) BOXES MORE THATN 1/4" FROM BOX TO SURFACE TO HAVE AN APPROVED EXTENDER RING-METAL NOT APPROVED AND FLUSH IN COMBUSTIBLES (ROOF: TIGHTEN LOOSE CONDUIT AND SEAL TITE FITTINGS 2) PROTECT SEAL TITE WHERE PASSSES THROUGH SHARP METAL EDGES) 7) FINISH SIGN POWER 8) SUPPORT FLEX CONDUIT AS PER CODE UNDER TELLERS 9) PANEL IN UPS SYSTEM TO HAVE A 90 AMP BREAKER 10) FINISH INSTALLATION OF DRIVE THROUGH EQUIPMENT | |
09/15/2003 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*( OK TO OCCUPY) 1) EMERGENCY LIGHTING BALLASTS NEED TO BE PLUGGED IN. 2) DISCONNECTS NEED TO BE IDENTIFIED AND MARKED WITH WITH PANEL AND CIRCUITS. |