Inspection Status: Approved
Inspection History: REINFORCED MASONRY PRE-GROUT
| Date |
Description |
Inspector |
Results |
Comments |
| 09/24/2003 |
REINFORCED MASONRY PRE-GROUT |
|
Approved |
|
| 07/18/2003 |
REINFORCED MASONRY PRE-GROUT |
|
Partial Approval |
IVRS - Inspection 0000* |
| 07/07/2003 |
REINFORCED MASONRY PRE-GROUT |
|
Denied |
IVRS - Inspection 0999*/ 1) CONCRETE AT TOP OF COLUMNS CAME BACK AT 1500 PSI INSTEAD OF 3000 PSI. ? TOPS ARE TO BE REMOVED AND REINSPECTED |
| 05/22/2003 |
REINFORCED MASONRY PRE-GROUT |
|
Partial Approval |
IVRS - Inspection 0000*COL TOPS OK TO POUR. |
| 05/16/2003 |
REINFORCED MASONRY PRE-GROUT |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) OK 2 SOUTH COLUMNS TO 12'-8" |
| 05/14/2003 |
REINFORCED MASONRY PRE-GROUT |
|
Partial Approval |
IVRS - Inspection 0000*1ST LIFT. |