Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/01/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*OK FINAL | |
| 03/31/2003 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*FINISH #1,2, & 5 OF PREVIOUS INSPECTION. | |
| 03/26/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* | |
| 03/24/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*1.) CLEAN DEBRITE FROM BUSS OF PANEL OR REPLACE 110-12. 2.) CORRECTLY IDENTIFY UNGROUNDED CONDUCTORS AT ALL LOCATIONS. 3.) PROPERLY GROUND ALL LIGHT FIXTURES. 4.) TIGHTEN LOOSE FITTINGS AND SUPPORT FLEX CONDUIT FOR WATER HEATER. 5.) OVER CURRENT PROJECTION TO BE SIZE FOR CONDUCTORS AS PER CODE 336-26. 6.) PLEASE COMPLETE #3 OF PREVIOUS INSPECTION. |