Permit: T03CM00266

Parcel: 140140520


Addresses:

5344 S PINE WY

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
02/18/2003 FRAMING Approved IVRS - Inspection 0000*/ 1) MAINTAIN MINIMUM EGRESS BEDROOM #5 2) COVERED WITHOUT INSPECTION 3) SPOT CHECK AREAS OF CONCERN 4) APPEAR ADEQUATE FOR PURPOSE INTENDED
02/10/2003 FRAMING Denied IVRS - Inspection 0999*/ 1) NAIL PROTECT WIRES WITHIN 1 1/4" OF STUD SURFACE AND PROVIDE BUSHING AT METAL ELECTRIC BOXES 2) OPEN ALL ELECTRIC BOXES CHECK FOR BUSHING AND GROUND 3) PROVIDE BUSHING AT ALL KNOCK OUTS 4) PROVIDE AN ISOLATED NEUTRAL BAR ON SUB PANEL WITH NEUTRAL AND GROUND TO MAIN PANEL 5) 14 GAUGE WIRE ON 20 AMP CIRCUIT NOT ALLOWED 6) CANNOT APPROVED UNTIL ELECTRIC COMPLETE 7) BLOCK DUCTS
02/04/2003 FRAMING Denied IVRS - Inspection 0999*