Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T03CM00264
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/14/2003 | FRAMING | Approved | IVRS - Inspection 0000*SEE PREVIOUS NOTES REGARDING MECH. DUCT PENETRATIONS MAINTAIN 1 HR. RATING W/ALL PENETRATION ELEC. ETC. | |
05/13/2003 | FRAMING | Denied | IVRS - Inspection 0999*NEED BOTH SIDES OF 1HR WALL ALSO GET PERMIT FOR MECH. WORK NEED DAMPERS IN WALL. CHECK OPENING. | |
05/02/2003 | FRAMING | Denied | IVRS - Inspection 0999*GET REVISION FROM ARCHITECT SHOWING WHAT YOU PROPOSE TO DO OR BUILD PARTITION ACCORDING TO PLANS. | |
04/24/2003 | FRAMING | Denied | IVRS - Inspection 0999*INSTALLATION DOESN'T MATCH THE APPROVED PLANS. PLANS SHOW EXTENDING THE WALL TO THE ROOF DECK. ALSO PLANS CALL FOR SCREW PATTERN @ 8" AT PERIMETER @ 12" IN THE FIELD. POST SUITE #236 IN HALLWAY. |