Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 08/16/2004 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection :* |
| 07/13/2004 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection :*/ 1) ROOF: USE APPROVED FITTING FOR SEAL TITE AND SUPPORT UP OFF ROOF 2) GROUNDING EQUIPMENT CONDUCTOR TO BE GREEN ENTIRE LENGTH AND CORRECT SIZE PER 250.119 + 250.122 3) TIGHTEN RECEPTACLE BOX 4) OK TEMP POWER |
| 07/07/2004 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection :*/ 1) HOOD TO USE APPROVED CONNECTOR NOT A BUSHING 2) AN APPROVED EXTENDER RING IS NEEDED WHERE DEVICE IS IN COMBUSTIONS 3) SWITCHES TO BE GROUNDED 4) WATER HEATER TO HAVE DISCONNECTING MEANS AND TIGHTEN FITTING 5) LABEL BREAKERS 6) FINISH OUTSIDE SOFFITS 7) BREAKER AMPACITY FOR NM CABLE TO BE AS PER 336.26 8) CLEAN BUSS OF FOREIGN MATERIAL |