Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - PROGRESS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/12/2004 | PLUMBING - PROGRESS | Approved | IVRS - Inspection :* | |
| 08/10/2004 | PLUMBING - PROGRESS | Partial Approval | IVRS - Inspection :*/ 1) OK TO BACKFILL WATER SERVICE UP TO BACKFLOW PREVENTER 2) OK TO BACKFILL TRENCH FROM BLDG DRAIN TO 40' DOWN STREAM | |
| 08/07/2004 | PLUMBING - PROGRESS | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) SHALL EXPOSE HCS CONNECTION 2) WATER LINE DOWNSTREAM OF METER SHALL DOWNSTREAM OF METER SHALL HAVE MINIMUM 12" OF COVER 3) HAVE ON SITE AT TIME OF INSPECTION CLEAN FILL FOR BLDG SEWER AND WATER |
|
| 08/03/2004 | PLUMBING - PROGRESS | Not ready for Inspection | IVRS - Inspection :*/ 1) NO SEWER INSTALLED 2) YARD WATER: NATIVE SOILS ARE TO ROCKY. PLEASE SHADE PVC WITH CLEAN FILL AND RECALL FOR INSPECTION. INSTALL 2" SHUT OFF VALVE IN CONC. VALVE BOX W/CI COVER AS NOTED ON P-1 |