Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/19/2004 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000*/ 1) OK FOR FINAL C OF O |
| 03/16/2004 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) EXTEND SEWER VENTS 2' ABOVE OUTSIDE AIR INTAKE ON A/C UNIT. EXTEND WTR HTR VENT 2' ABOVE WALL ON ROOF. 2) EVAP COOLER DRAIN BACK PITCHED AT OUTLET OR UNIT. DRAIN IS LEAKING. CANNOT TERMINATE DIRECTLY INTO A SEWER VENT. |
| 03/05/2004 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ OK FOR TEMP POWER FOR TESTING. |