Inspection Status: Approved
Inspection History: MECHANICAL - HOOD SYSTEMS
| Date |
Description |
Inspector |
Results |
Comments |
| 03/01/2004 |
MECHANICAL - HOOD SYSTEMS |
|
Approved |
IVRS - Inspection 0000* |
| 02/25/2004 |
MECHANICAL - HOOD SYSTEMS |
|
Denied |
IVRS - Inspection 0999*/ 1) BONDING ON FIRE WRAP NOT TIGHT ENOUGH AND NOT INSTALLED PER MANUFACTURERS INSTRUCTIONS. YOU CANNOT USE 2 DIFFERENT PRODUCTS ON FIRE WRAP SYSTEM. PROVIDE INSTALL INSTRUCTIONS FOR FIRE WRAP. METAL SLEEVES ARE TO LONG ON ACCESS DOOR. DO NOT TAPE WRAP TO ACCESS DOOR. WRAP MUST EXTEND ALL THE WAY TO TOP OF GREASE DUCT |