Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T03CM00185
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/09/2003 | PLUMBING - FINAL | Approved | IVRS - Inspection 0000*/ 1) CORRECTIONS MADE-OK 2) PLUMBING FINAL-OK 3) OK FOR C OF O PENDING ANY OTHER INSPECTIONS 4) BUILDING INSPECTOR WILL BE ASKED TO CHECK THE ACCESS PANEL IN THE RESTROOM | |
07/08/2003 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection 0000* 1) NOT READY FOR INSPECTION REINSPECTED @ 3:OO PM. 1) T&P RELIEF DRAIN MAY NOT BE COMBINED WITH PAN DRAIN. A LAVATORY TAILPIECE IS NOT AN APPROVED TERMINUS FOR T&P RELIEF. 3) SEE REMARK #6 OF PLUMBING EQUIPMENT SCHEDULE M2,0. 4) SEE GENERAL NOTES DOMESTIC WATER... ALL WATER PIPING SHALL BE INSULATED. | |
07/07/2003 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999*1) COPPER ABOVE CEILING NOT SUPPORTED PER TABLE 3-1 94 UPC. 2) HOT INSULATION NOT PER PLAN. SEE GENERAL NOTES DOMESTIC WATER. 3) REVIEW 511.2 94 UPC LOCATION AND ACCESS OF WATER HEATER. 4) EXPANSION TANK NOT SUPPORTED. 5) MAY NOT CONBINE T&P RELIEF DRAIN AND PAN DRAIN. 6) INSPECTION TERMINATED-CHECK ALL WORK TO CONFIRM TO 94 UPC AND APPROVAL PLAN |