Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T03CM00185
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/17/2003 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection 0000*/ 1) OK CORRECTIONS FROM 6/16/03 COMPLETE | |
06/16/2003 | PLUMBING - INTERMEDIATE | Denied | 1) NO PROVISION MADE ON SOPPER HOT SIDE FOR INSULATION 2) CAP OFF ALL DEMO'D PIPING IN THE WALL AND HAVE INSPECTED 3) TRAP PRIMER SHOULD DROP VERTICALLY AT LEAST 12" ON THE DISCHARGE SIDE TO AVOID WATER BACKING UP AND OVER FLOWING PRIMER 4) NEED TO SEE CLOSET FLANGE 5) REVIEW 511.2 AND 511.3 94 UPC LOCATION AND ACCESS TO WATER HEATER |