Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date |
Description |
Inspector |
Results |
Comments |
| 10/21/2003 |
ELECTRIC - CABLE DROP |
|
Approved |
IVRS - Inspection 0000* |
| 10/17/2003 |
ELECTRIC - CABLE DROP |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 10/16/2003 |
ELECTRIC - CABLE DROP |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) BONDING DEVICES NEEDED ON ALL SIDES OF NIPPLES AND RISER 250.94 2) GROUNDING ELECTRODE TO BE CONNECTED TO GROUNDED TERMINAL 250.24 3) A PERMANENT METAL ADDRESS LABEL IS NEEDED 4) WHERE IS PLAN REVISION FOR GROUNDING ELECTRODE CONDUCTOR |