Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date |
Description |
Inspector |
Results |
Comments |
| 07/17/2003 |
ELECTRIC - CABLE DROP |
|
Approved |
IVRS - Inspection 0000*SENT TO TEP ON 7/18AM |
| 07/15/2003 |
ELECTRIC - CABLE DROP |
|
Denied |
IVRS - Inspection 0999* 1) GROUNDING INCOMPLETE 2) TRENCHING INCOMPLETE 3) PIPING & TEST IMCOMPLETE NO PLANS/PERMIT VISIBLE |
| 07/11/2003 |
ELECTRIC - CABLE DROP |
|
Denied |
IVRS - Inspection 0210*/ 1) NO RISER OR SUPPORTS 2) TRENCH NOT COMPLETED 3) NO SEWER LINE OR CONNECTION |
| 07/09/2003 |
ELECTRIC - CABLE DROP |
|
Denied |
IVRS - Inspection 0999* |
| 05/09/2003 |
ELECTRIC - CABLE DROP |
|
Not ready for Inspection |
IVRS - Inspection 0000*RISER NOT IN PLACE |