Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/01/2004 |
BUILDING - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 02/27/2004 |
BUILDING - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) RECALL WHEN STAIR COMPLETED |
| 02/24/2004 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) INSTALL DRIP LEGS AT GAS APPLIANCES 2) 3-SCREW WATER HEATER FLUE 3) INSTALL OUTLET AT ENTRY, COMPLETE KITCHEN COUNTER OUTLETS 5) REMOVE PAINT AT GAS BOND 6) INSTALL UNION AT TPR 7) STAIR RUN 9 1/2" REQUIRES 10" 8) 3/8" MAXIMUM DIFFERENCE IN RISE AND RUN 9) BARE WIRING IN MASTER CLOSET 10) OUTLET MISSING IN SECOND FLOOR BEDROOM SOUTH/EAST 11) COMBUSTION RETURN WITHIN 12" OF CEILING AND FLOOR 12) SEAL LID IN FURNACE ROOM 13) 1" CLEARANCE REQUIRED AT B-VENT 14) 6" CLEARANCE AT DOOR TO SINGLE WALL VENT AND DRYWALL |
| 02/23/2004 |
BUILDING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* |