Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T03CM00146

Parcel: 116213870


Addresses:

458 S STEPHANIE LP

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
10/29/2003 FRAMING Approved IVRS - Inspection 0000*
10/27/2003 FRAMING Partial Approval IVRS - Inspection 0000*/ 1) FIRE STOPPING 2ND FLOOR SHAFT 2) SHIM HEADERS. 3) SEAL FLOOR/CEILING PENETRATIONS. 4) DUER BLOCKING.
10/21/2003 FRAMING Denied IVRS - Inspection 0999*/ 1) BLOCK OUT FURNACE AT LID 2) STRAP PLATE AT DRYER VENT 3) SHIM HEADER AT GARAGE WINDOW REAR SLIDER ALTERNATE AT GARAGE POST TO BEAM 4) FIRE STOP TOP PLATE IN FURNACE ROOM 5) ANCHOR STAIR PER DETAIL 6) INSTALL GPC OR APPROVED 7) SEAL FLOOR PENETRATIONS 8) INSTALL POST AT DINING EXTERIOR WALL 9) NAIL PLATE IN FURNACE THROUGHOUT 10) SMOKE DETECTOR IN OFFICE/BR 11) NAIL PLATE WASTE IN FURNACE ROOM, NEAR FRONT DOOR, HALL BATH 12) TEST WASTE 13) SUPPORT WASTE FROM 2ND FLOOR 14) 1" CLEARANCE AT FURNACE FLUE 15) SUPPORT DUCT NEAR FIREPLACE 16) INSTALL HEAT SHIELD AND BLOCK OUT FIRE STOP SPACER PER DETAIL