Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 04/23/2003 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 03/11/2003 |
FRAMING |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) TRUSS REPAIR DOCUMENT MUST BE APPROVED BY CITY OF TUCSON |
| 03/10/2003 |
FRAMING |
|
Denied |
IVRS - Inspection 0950*/ 1) GLU LAM IN GARAGE NOT CLIPPED. PROVIDE DETAIL 2) NOT COMPLETE 2ND FLOOR FRONT 3) WATER HEATER ELECTRIC BOX DAMAGED BY NAIL 4) STUDS WITH HOLDOWNS NOT CLIPPED 5) HOLDOWN BOLTS LOOSE 6) STOPPED INSPECTION TO MANY ITEMS |
| 03/06/2003 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) LATH NOT COMPLETE |
| 03/03/2003 |
FRAMING |
|
Denied |
IVRS - Inspection 0950*/ 1) LATH NOT COMPLETE 2) HOUSE NOT COMPLETE ENOUGH TO INSPECT |