Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 03/10/2003 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 03/05/2003 |
FRAMING |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) DWV OK-GAS-OK 2) A BOLTS GARAGE TO HOUSE SHEAR WALL 2) HOLES DRILLED FOR WATER LINES EXCEEDS MAXIMUM 3) NEED POSITIVE PITCH ON FLAT VENT HALL CEILING 1ST FLOOR 4) LEDGER AT KITCHEN A3.5 USING 10D'S SPLITTING STUDS 5) RETRUN PLENIUM HOLE IN FLOOR 6) 10" FROM NOSING 7) LAG FOR WALKING DECK INTO BACK OF FLOOR JOIST NOT BLOCKS ADD 1 IN BETWEEN EXISTING BOLTS |