Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date |
Description |
Inspector |
Results |
Comments |
| 02/20/2003 |
EXT METAL CLIPS/EXT SHEATHING |
|
Approved |
IVRS - Inspection 0000* |
| 02/19/2003 |
EXT METAL CLIPS/EXT SHEATHING |
|
Denied |
IVRS - Inspection 0999*/ 1) REVISE DETAIL 15 PAGE A-8 TO SHOW LAG BOLTS 2) HOUSE WRAPPED BEFORE 1025 APPROVED |
| 02/18/2003 |
EXT METAL CLIPS/EXT SHEATHING |
|
Denied |
IVRS - Inspection 0999*/ 1) ITEM 5 OF 2/14/03 NOT COMPLIED WITH AT BAY WINDOW DINING ROOM 2) 15/A8 NOT COMPLIED WITH |
| 02/14/2003 |
EXT METAL CLIPS/EXT SHEATHING |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) HIP ROOF EAST SIDE, OSB RUN PARALELL TO TRUSSES BLOCK AT 24" ON CENTER AND NAIL 2) RE-NAIL AT DECK TO LEDGER WITH 8D'S 3) RUN SHEAR UP TO CHORD REAR WALL WEST SIDE 4) LEDGER TO STUDS FOR DINING ROOM, STUDS ARE SPLIT AT ATTACHEMENT TO LEDGER FULL BEARING AT DOUBLE GIRDER NO HOLDING POWER FOR NAILS THAT WERE DRIVEN INTO STUDS 5) NEED FULL BEARING AT DOUBLE GIRDER 3 PT BEARING 6) STRAP GARAGE POST 7) NEED HANGERS FOR SHED ROOF GARAGE 2 X 4 TOP CHORD 8) WALKING DECK REQUIRES H2.5 AT LEDGER, OR USE LAG BOLT |