Permit: T03CM00122

Parcel: 115081020

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
06/18/2003 PLUMBING - FINAL Approved IVRS - Inspection 0000*/ 1) CORRECTIONS LISTED CORRECTED 2) PLEASE SEE #9 ABOVE
06/16/2003 PLUMBING - FINAL Denied IVRS - Inspection 0999*/ 1) HOUSE LOCKED-NO ACCESS 2) SEE NOTE #7 AND 8 ABOVE (REMEBER ABS VENTS TO BE PAINTED WITH FLAT LATEX PAINT)
01/09/2003 PLUMBING - FINAL Denied 1. ALL FIXTURES TO BE CAULKED 408.2 94 UPC
2. ALL HOSE BIBBS TO HAVE ATMOSPHERIC VACUUM BREAKERS 602 94 UPC
3. N/H BAND NOT APPROVED LISTED CONNECTOR AT TRAP ARM 301.1.3 94 UPC
4. TRAPS SHALL BE THE SAME SIZE AS THE TRAP ARM TO WHICH IT IS CONNECTED. 1003.3 94 UPC THE TRAP ARM SHALL NOT CHANGE SIZE.
5. ALL SINKS REQUIRE CLEAN OUTS 707.4 UPC
6. APPLIANCE CONNECTOR AT WATER HEATER EXCEEDS ALLOWABLE LENGTH 1212.0 94 UPC
7. VENT TERMINATION WITHIN 10' OF AIR INTAKE 906.2 94 UPC
8. WATER HEATER VENT TERMINATION 517 94 UPC
9. THIS INSPECTION COVERS ONLY VISIBLE WORK, AND DOES NOT INCLUDE ANY WORK PERFORMED WITHOUT PERMITS THAT HAS BEEN COVERED OR CONCEALED.
10. ONLY ONE SLIP NUT ALLOWED ON OUTLET SIDE OF P-TRAP.